Keep up to dateSummary of requirements for 30 mA RCD protection | |||
Regulations | Relating to | Example | Additional protection |
411.3.3 | All socket-outlets up to | Downstairs sockets | 30 mA RCD or RCBO |
20 A rating for general use | Upstairs sockets | ||
by ordinary persons | Kitchen sockets | ||
Cooker outlet with | |||
integral 13 A socket-outlet. | |||
Any other socket rated | |||
up to 20 A including garage. | |||
701.411.3.3 | All electrical circuits | Shower circuit | 30 mA RCD or RCBO |
in a room with a | Lighting circuit | ||
fixed bath or shower | Heating circuit | ||
Ventilation circuit | |||
Shaver socket | |||
Socket-outlets | |||
522.6.6 | All electrical circuits buried | All concealed wiring | 30 mA RCD or RCBO |
522.6.7 | in a wall or partition at depth | - Socket-outlets | |
522.6.8 | of less than 50 mm and | - Lighting circuits | |
without earthed | - Smoke alarms | ||
mechanical protection | - Burglar alarms |