Table 1: Insulation thickness to BS 5422: 2001 | ||||
Application | Steel pipe size NB (mm) | Kingspan Kooltherm | Kingspan Kooltherm zero odp | Mineral fibre |
Environmental thickness (mm) of insulation | 50 | 20 | 25 | 38 |
for non-domestic hot water | 100 | 25 | 25 | 43 |
(60°C) to control heat loss. | 200 | 30 | 30 | 47 |
Environmental thickness (mm) of insulation | 50 | 20 | 25 | 38 |
for non-domestic heating installations (75°C) | 100 | 25 | 25 | 42 |
to control heat loss. | 200 | 30 | 30 | 45 |
Environmental thickness (mm) of insulation | 50 | 20 | 25 | 48 |
for chilled water supplies (water at 0°C) to | 100 | 25 | 35 | 63 |
control heat gain. | 200 | 35 | 40 | 75 |