Table 1: Separation distances between power and signal cables | |||
Signal cable | Power cable | ||
Twin & earth (mm) | Steel wire amoured (mm) | MICC (mm) | |
Plain | 150 | 125 | Touching |
UTP | 75 below 100 MHz | 50 | Touching |
125 above 100 MHz | |||
Screened | Touching | Touching | Touching |
Table 2: Types of cable screens | ||
Cable Type | Noise reduction | |
50 Hz magnetic | RF | |
Plain (no screen, no twist) | none | none |
Twisted pair | good | none |
MICC | none | good |
Twisted pair MICC | good | good |
Plain in steel trunking or conduit | good | good |
Plain with braid or metal tape screen | none | good |
Twisted pair with braid or metal tape screen | good | good |
Steel wire armoured | good | good |
Plain in correctly designed and installed aluminium trunking or conduit | none | good |
Twisted pair in correctly designed and installed aluminium trunking or conduit | good | good |