- News
All the latest updates on building safety reformRegulations latest
- Focus
All the latest updates on building safety reform
TABLE 1: SELECTED ENVIRONMENTAL CRITERIA FROM TABLE 1.1 IN SECTION A1 | ||||||||||
Building type | Winter dry resultant temp range for stated activity and clothing levels | Summer dry resultant temp range for stated activity and clothing levels | Suggested outdoor supply rate | Filtration guide | Maintained illuminance | Noise rating | ||||
Temp | Activity | Clothing | Temp | Activity | Clothing | (lux) | (nr) | |||
(ºC) | (met) | (clo) | (ºC) | (met) | (clo) | |||||
Offices | ||||||||||
Executive | 21-23 | 1·2 | 0·85 | 22-24 | 1·2 | 0·7 | Table 1·10 | 7 | 500 | 30 |
General | 21-23 | 1·2 | 0·85 | 22-24 | 1·2 | 0·7 | Table 1·10 | 6-7 | 500 | 35 |
Open-plan | 21-23 | 1·2 | 0·85 | 22-24 | 1·2 | 0·7 | Table 1·10 | 6-7 | 500 | 35 |
Museums and art galleries | ||||||||||
Display | 19-21 | 1·4 | 1·0 | 21-23 | 1·4 | 0·65 | Table 1·10 | 7-8 | 200 | 30-35 |
Storage | 19-21 | 1·4 | 1·0 | 21-23 | 1·4 | 0·65 | Table 1·10 | 7-8 | 50 | 30-35 |
TABLE 2: Recommended outdoor air supply rates for sedentary occupants (TABLE 1.10) | ||
Level of smoking | Proportion of occupants that smoke (%) | Outdoor air supply rate (litres/s/person) |
No smoking | 0 | 8 |
Some smoking | 25 | 16 |
Heavy smoking | 45 | 24 |
Very heavy smoking | 75 | 36 |
Continuous heavy smoking* | 100 | 43 |
*Rooms set aside for smoking. | ||