Part L: Fan and system efficiencies for a typical AHU
Unit referenceAHU 1 SUPPLYAHU 1 EXTRACT
Design criteria  
Design capacity (m3/s)2217.1
Design static (Pa)1089696
Quantity of velocity pressures11
Max w/l/s2.52.5
Max system input power / kw5542.75
   
Preselection criteria  
Max discharge velocity1212
Nominal dynamic (based on above discharge velocity)86.486.4
Nominal total pressure1175.4782.4
Nominal required system efficiency to meet pressure47.02%31.30%
   
Selected fan data  
Dynamic (Pa)112107
Shaft power (kW)28.415.84
Installed motor power (kW)2 x 302 x 15
Fan shaft efficiency93.04%86.69%
Based on2 x 8002 x 710
Motor efficiency (nominal)93.40%93.40%
Based on   
Belt drive efficiency (nominal)94.00%94.00%
Based on belt drivebelt drive
Inverter efficiency (nominal)96.50%96.50%
Based on Danfoss VLT6000 at 75% load  
Total tolerance of fanset components0.00%0.00%
Based onNot consideredNot considered
Actual system input power (kW)33.5218.7
Max actual system input power (kW including tolerances)33.5218.7
System heat loss per volume flow rate (W/ l /s)1.521.09
Max (W/ l/s) including tolerances1.521.09
Total system efficiency78.82%73.44%
Worst case total system efficiency including tolerances78.82%73.44%
   
Reselection criteria  
Max static (Pa based on above component efficiencies) 1858.61729.1
Max total pressure (Pa based on above component efficiencies) 1970.561836.11
System heat loss per volume flow rate (W / l /s)2.3735 
(with supply and extract powers/supply air vol)  
Heat wheel heat recovery Winter74.30%
 Summer76.00%
   
Air Pressure drop on the AHUS   
Volume (m3/s)2217.1
External static pressure (Pa)300250
Louvre (Pa)INCINC
Damper (Pa)4075
Electric frost (Pa)200
Panel/bag AHU 1 clean (Pa)18887
Thermal wheel (Pa)158117
Cooler & eliminator (Pa)2090
Electric heater (Pa)200
Atmospheric attenuation (Pa)1614
Non-return dampers (Pa)7070
Diffuser (Pa)5045
Jobside attenuation (Pa)1838
Totals1089696