| Table 1: Floor space allowance for services (as a percentage of floor area) | |||
| Design area | Application | Other information | Rule of thumb |
| All services | Simple factory | 4% | |
| Offices and commercial | 6-10% | ||
| Hi-tech building | 15-30% | ||
| Air conditioning (excluding boilers and refrigeration) | Fan coil system | 1·5-2·5% | |
| VAV system | 3-4·5% | ||
| Cooling towers and air-cooled condensers | 0.3-1·5% | ||
| Electrical services (excluding sub-stations and standby generation sets) | 0·5-1·5% | ||
| Lift motor rooms | 0·2-0·5% | ||
| Refrigeration (excluding cooling towers) | Central plant | 1-2% | |
| Ventilation | Toilet extract | 0.3-1·0% | |
| Supply and extract systems | 3-5% | ||
| All air low velocity system | 4-6% | ||
| Table 2: Space allowances for service ducts and shafts | |||
| Design area | Application | Other information | Rule of thumb |
| Air ducting | Typical ducting size | 0·2 m2/m3/s | |
| Lift shafts | Between 4-18 floors in office type buildings | Internal shaft area | |
| A: floor area/storey (250 m2 min) | |||
| N: floors | 3 + A(n-4)/250 m2 | ||
| Mechanical service riser | Simple pipework riser | Depth needed to open access door/size panel when width of door varies with /type of pipe or depth of service/duct | |
| 690 mm | |||
| Pipework | Pipe: 20 mm diamter | 100 mm x 100 mm | |
| Pipe 25 mm diameter | 120 mm x 120 mm | ||
| Pipe: 32 mm diameter | 130 mm x 130 mm | ||
| Three-sided riser | Minimum depth from service to (open) acess door/panel | 690 mm | |
| Service ducts | Vertical service duct | Floor space served by vertical service (radius) | 15-23 m |
| Aspect ratio of vertical service duct | 2:1 to 4:1 | ||
| Total duct areas as a percentage of gross floor area | 2% | ||
| Table 3: Space allowances for plant rooms (floor area) | |||
| Design area | Application | Other information | Rule of thumb |
| Air-cooled condensers and controls | Space for installation and maintenance | 25 + kW/200 m2 | |
| Air handling units | With extract/recirculation | 8 m2 per m3/s | |
| Without extract/recirculation | 5 m2 per m3/s | ||
| Boilers (percentage floor area) | Boiler plant and calorifiers | 0·8-1·8% | |
| Oil tank room | 1-2% | ||
| Boilers (floor area and height) | Boilers, pumps, piping and space for installation and maintenance | Output 100kW | 15 m2 x 3 m |
| Output: 200 kW | 25 m2 x 3 m | ||
| Output: 1000 kW | 80 m2 x 4 m | ||
| Output: 4000 kW | 140 m2 x 5 m | ||
| Calorifiers (floor area and height) | Calorifiers, pumps, pipework, installation and maintenance controls and space for | Vertical: (1 m3) | 10 m2 x 3 m |
| Vertical (5 m3) | 20 m2 x 4 m | ||
| Vertical (10 m3) | 25 m2 x 5 m | ||
| Vertical (15 m3) | 60 m2 x 3 m | ||
| Horizontal (1 m3) | 25 m2 x 3 m | ||
| Horizontal (5 m3) | 30 m2 x 3 m | ||
| Horixontal (10 m3) | 45 m2 x 3 m | ||
| Horizontal (15 m3) | 60 m2 x 3 m | ||
| Chillers (water cooled) | With pumps, pressurisation, pipework and control panels | Output: 1000 kW | 50 m2 x 3 m |
| Output: 2000 kW | 63 m2 x 3 m | ||
| Output: 3000 kW | 83 m2 x 3·5 m | ||
| Output: 4000 kW | 108 m2 x 4 m | ||
| Chillers (air-cooled) | Located outside, includes space for installation and maintenance | Output: 200 kW | 39 m2 |
| Output: 400 kW | 53 m2 | ||
| Output: 600 kW | 75 m2 | ||
| Output: 800 kW | 84 m2 | ||
| Output 1000 kW | 98 m2 | ||
| Output: 1200 kW | 116 m2 | ||
| Cold water storage | Single cold water tank. Includes space for installation and maintenance but add space for pressurisation plant or circulation pumps | FA: floor area | |
| V: gross storage m2 | |||
| 1 m high | FA: 10 + V/0·75 m2 | ||
| 2 m high | FA: 10 + V/1·6 m2 | ||
| 3 m high | FA: 10 + V/2.4 m2 | ||
| Cold water storage | Minimum storage for hot and cold outlets | Office – with canteen | 45 litres/person |
| Office – no canteen | 40 litres/person | ||
| Hotel | 135 litres/bed space | ||
| Hostel | 90 litres/bed space | ||
| Restaurant | 7 litres/meal | ||
| Day school | 15-20 litres/pupil | ||
| Boarding school | 90 litres/pupil | ||
| Children’s home or residential nursery | 135 litres/bed space | ||
| Nurses’ home | 120 litres/bed space | ||
| Nursing or convalescent home | 135 litres/bed space | ||
| Hot water storage | Minimum storage capacity | Dwellings | 115 litres/bedroom |
| Students and nurses’ homes | 20 litres/bed space | ||
| Children’s home, elderly sheltered and elderly care home | 25 litres/bed space | ||
| Hostels, budget | 35 litres/bedroom | ||
| Hotels, 4/5 star | 45 litres/bedroom | ||
| Offices, shops and factories | 5 litres/person | ||
| Schools: nursery, primary, secondary | 5 litres/person | ||
| Schools, boarding | 25 litres/person | ||
| Hospitals: district general, surgical ward and medical ward | 50 litres/bed | ||
| Hospitals: paediatric | 70 litres/bed | ||
| Hospitals: geriatric | 40 litres/bed | ||
| Sports changing: sports hall and swimming pool | 20 litres/person | ||
| Sports changing: field and all-weather pitch | 35 litres/person | ||
| Places of assembly such as libraries, museums and cinemas (excluding staff) | 1 litre/person | ||
| Cooling towers | FA: floor area (kW: heat rejection) | FA: 50 + Kw/66 m2 | |
| Sub-station | 200 kVA transformers | 47 m2 | |
| Switchgear | HV switchgear | 14 m2 | |
| HV + lv switchgear | 27 m2 | ||
| Standby generation | Standby sets and accessories | FA: floor area | FA: 15 + kVA/30 m2 |
| Uninterruptible power supply | Single module system (add space for batteries) | ||
| FA: floor area | FA: (2+ kW/200) x 2 m2 | ||
| Table 4: Miscellaneous services | |||
| Design area | Application | Other information | Rules of thumb |
| Control panels and distribution boards | Front panel controls, wall mounted or floor standing | Fixed height range (above finished floor or operating platform level) | 1200-1800 mm |
| LTHW boiler plant (component criteria for leakage containment) | Oil storage tanks, distilate and residual fuel oils | If tank fails, walls and doors treated to contain spillage | Tank contents + 10% |
| Table 5: Space allowances for on-floor services (depth of clear space in ceiling/floor void) | |||
| Design area | Application | Other information | Rule of thumb |
| Air conditioning | VAV | 350-750 mm | |
| VRV | 450 mm | ||
| Recessed chilled beams | 350-450 mm | ||
| Surface chilled beams | 250 mm | ||
| Chilled ceilings | 250 mm | ||
| Fan coils | 450 mm | ||
| Ducted air systems | 450 mm | ||
| Drainage | 100 mm diameter | 10-25 mm per m run | |
| Solid waste | 150 mm diamtere | 7-16 mm per m run | |
| Lighting | Fluorescent | 100-150 mm (+access) | |
| Downlighter | 150-300 mm | ||
| Power and communications | Multi-core cables and lighting cables | 100-200 mm | |
| Power and data (heavy line) | 200-250 mm | ||
| Computer rooms | 300 mm | ||
| Table 6: Space allowances for catering facilities | |||
| Design area | Application | Other information | Rule of thumb |
| Kitchen and dining facilities | Kitchens including preparation and storage | Minimum needs: | |
| Up to 100 meals | 0·4 m2/meal | ||
| Up to 500 meals | 0·25 m2/meal | ||
| For single sittings | Ratio of kitchen space to dining space | 0·33:1 to 0·5:1 | |
| For multiple sittings | Ratio of kitchen space to dining space | 1:1 | |
| Table 7: Floor allowance per occupant (net internal area) | |||
| Design area | Application | Other information | Rule of thumb |
| General offices | 12-17 m2/person | ||
| Trading desks, call centres, workstations | 4-6 m2/person | ||
| Enclosed offices | 15 m2 (or more) per person | ||
| Table 8: Plant weight allowances | |||
| Design area | Application | Other information | Rule of thumb |
| Single boiler | 500 kW | 1500 kg | |
| 1500 kW | 4250 kg | ||
| 2500 kW | 6500 kg | ||
| Single storage steel calorifier | 4 m3 | 1250 kg | |
| 8 m3 | 2500 kg | ||
| 12 m3 | 3300 kg | ||
| Single non-storage mild steel heating calorifier | 500 kW | 150 kg | |
| 1000 kW | 225 kg | ||
| 1500 kW | 275 kg | ||
| 2000 kW | 325 kg | ||
| Single water cooled liquid chiller | 1500 kW | 10 000 kg | |
| 3000 kW | 20 000 kg | ||
| 4500 kW | 30 000 kg | ||
| Single air-cooled liquid chiller | 500 kW | 6000 kg | |
| 1000 kW | 11 000 kg | ||
| 1500 kW | 14 000 kg | ||
| Single generator | 500 kVA | 5000 kg | |
| 1000 kVA | 8000 kg | ||
| 1500 kVA | 11 0000 kg | ||
| Single ups system | 100 kVA | 1250 kg | |
| 300 kVA | 2750 kg | ||
| 500 kVA | 4250 kg | ||