Table 1: Floor space allowance for services (as a percentage of floor area)
Design areaApplicationOther informationRule of thumb
All servicesSimple factory 4%
 Offices and commercial 6-10%
 Hi-tech building 15-30%
Air conditioning (excluding boilers and refrigeration)Fan coil system 1·5-2·5%
 VAV system 3-4·5%
Cooling towers and air-cooled condensers  0.3-1·5%
Electrical services (excluding sub-stations and standby generation sets)  0·5-1·5%
Lift motor rooms  0·2-0·5%
Refrigeration (excluding cooling towers)Central plant 1-2%
VentilationToilet extract 0.3-1·0%
 Supply and extract systems  3-5%
 All air low velocity system 4-6%
Table 2: Space allowances for service ducts and shafts
Design areaApplicationOther informationRule of thumb
Air ducting Typical ducting size0·2 m2/m3/s
Lift shaftsBetween 4-18 floors in office type buildingsInternal shaft area 
  A: floor area/storey (250 m2 min) 
  N: floors3 + A(n-4)/250 m2
Mechanical service riserSimple pipework riserDepth needed to open access door/size panel when width of door varies with /type of pipe or depth of service/duct 
   690 mm
Pipework Pipe: 20 mm diamter100 mm x 100 mm
  Pipe 25 mm diameter 120 mm x 120 mm
  Pipe: 32 mm diameter130 mm x 130 mm
 Three-sided riserMinimum depth from service to (open) acess door/panel690 mm
Service ductsVertical service ductFloor space served by vertical service (radius)15-23 m
  Aspect ratio of vertical service duct2:1 to 4:1
  Total duct areas as a percentage of gross floor area2%
Table 3: Space allowances for plant rooms (floor area)
Design areaApplicationOther informationRule of thumb
Air-cooled condensers and controls Space for installation and maintenance25 + kW/200 m2
Air handling units With extract/recirculation8 m2 per m3/s
  Without extract/recirculation5 m2 per m3/s
Boilers (percentage floor area)Boiler plant and calorifiers 0·8-1·8%
  Oil tank room1-2%
Boilers (floor area and height)Boilers, pumps, piping and space for installation and maintenanceOutput 100kW15 m2 x 3 m
  Output: 200 kW25 m2 x 3 m
  Output: 1000 kW 80 m2 x 4 m
  Output: 4000 kW140 m2 x 5 m
Calorifiers (floor area and height)Calorifiers, pumps, pipework, installation and maintenance controls and space forVertical: (1 m3)10 m2 x 3 m
  Vertical (5 m3)20 m2 x 4 m
  Vertical (10 m3)25 m2 x 5 m
  Vertical (15 m3)60 m2 x 3 m
  Horizontal (1 m3)25 m2 x 3 m
  Horizontal (5 m3)30 m2 x 3 m
  Horixontal (10 m3)45 m2 x 3 m
  Horizontal (15 m3)60 m2 x 3 m
Chillers (water cooled)With pumps, pressurisation, pipework and control panelsOutput: 1000 kW50 m2 x 3 m
  Output: 2000 kW63 m2 x 3 m
  Output: 3000 kW83 m2 x 3·5 m
  Output: 4000 kW108 m2 x 4 m
Chillers (air-cooled) Located outside, includes space for installation and maintenanceOutput: 200 kW39 m2
  Output: 400 kW53 m2
  Output: 600 kW75 m2
  Output: 800 kW84 m2
  Output 1000 kW98 m2
  Output: 1200 kW116 m2
Cold water storageSingle cold water tank. Includes space for installation and maintenance but add space for pressurisation plant or circulation pumpsFA: floor area 
  V: gross storage m2 
  1 m highFA: 10 + V/0·75 m2
  2 m highFA: 10 + V/1·6 m2
  3 m highFA: 10 + V/2.4 m2
Cold water storageMinimum storage for hot and cold outletsOffice – with canteen45 litres/person
  Office – no canteen40 litres/person
  Hotel135 litres/bed space
  Hostel90 litres/bed space
  Restaurant7 litres/meal
  Day school15-20 litres/pupil
  Boarding school90 litres/pupil
  Children’s home or residential nursery135 litres/bed space
  Nurses’ home120 litres/bed space
  Nursing or convalescent home135 litres/bed space
Hot water storageMinimum storage capacityDwellings115 litres/bedroom
  Students and nurses’ homes20 litres/bed space
  Children’s home, elderly sheltered and elderly care home25 litres/bed space
  Hostels, budget35 litres/bedroom
  Hotels, 4/5 star45 litres/bedroom
  Offices, shops and factories5 litres/person
  Schools: nursery, primary, secondary5 litres/person
  Schools, boarding25 litres/person
  Hospitals: district general, surgical ward and medical ward50 litres/bed
  Hospitals: paediatric70 litres/bed
  Hospitals: geriatric40 litres/bed
  Sports changing: sports hall and swimming pool20 litres/person
  Sports changing: field and all-weather pitch35 litres/person
  Places of assembly such as libraries, museums and cinemas (excluding staff)1 litre/person
Cooling towers FA: floor area (kW: heat rejection)FA: 50 + Kw/66 m2
Sub-station200 kVA transformers 47 m2
 SwitchgearHV switchgear14 m2
  HV + lv switchgear27 m2
Standby generationStandby sets and accessoriesFA: floor areaFA: 15 + kVA/30 m2
Uninterruptible power supplySingle module system (add space for batteries)  
  FA: floor areaFA: (2+ kW/200) x 2 m2
Table 4: Miscellaneous services
Design areaApplicationOther informationRules of thumb
Control panels and distribution boardsFront panel controls, wall mounted or floor standingFixed height range (above finished floor or operating platform level)1200-1800 mm
LTHW boiler plant (component criteria for leakage containment)Oil storage tanks, distilate and residual fuel oilsIf tank fails, walls and doors treated to contain spillageTank contents + 10%
Table 5: Space allowances for on-floor services (depth of clear space in ceiling/floor void)
Design areaApplicationOther informationRule of thumb
Air conditioningVAV 350-750 mm
 VRV 450 mm
 Recessed chilled beams 350-450 mm
 Surface chilled beams 250 mm
 Chilled ceilings 250 mm
 Fan coils 450 mm
 Ducted air systems 450 mm
Drainage 100 mm diameter10-25 mm per m run
 Solid waste150 mm diamtere7-16 mm per m run
LightingFluorescent 100-150 mm (+access)
 Downlighter 150-300 mm
Power and communicationsMulti-core cables and lighting cables 100-200 mm
 Power and data (heavy line) 200-250 mm
 Computer rooms 300 mm
Table 6: Space allowances for catering facilities
Design areaApplicationOther informationRule of thumb
Kitchen and dining facilitiesKitchens including preparation and storageMinimum needs: 
  Up to 100 meals0·4 m2/meal
  Up to 500 meals0·25 m2/meal
 For single sittingsRatio of kitchen space to dining space0·33:1 to 0·5:1
 For multiple sittingsRatio of kitchen space to dining space1:1
Table 7: Floor allowance per occupant (net internal area)
Design areaApplication Other informationRule of thumb
General offices  12-17 m2/person
Trading desks, call centres, workstations  4-6 m2/person
Enclosed offices  15 m2 (or more) per person
Table 8: Plant weight allowances
Design areaApplicationOther informationRule of thumb
Single boiler500 kW 1500 kg
 1500 kW 4250 kg
 2500 kW 6500 kg
Single storage steel calorifier4 m3 1250 kg
 8 m3 2500 kg
 12 m3 3300 kg
Single non-storage mild steel heating calorifier500 kW 150 kg
 1000 kW 225 kg
 1500 kW 275 kg
 2000 kW 325 kg
Single water cooled liquid chiller1500 kW 10 000 kg
 3000 kW 20 000 kg
 4500 kW 30 000 kg
Single air-cooled liquid chiller500 kW 6000 kg
 1000 kW 11 000 kg
 1500 kW 14 000 kg
Single generator500 kVA 5000 kg
 1000 kVA 8000 kg
 1500 kVA 11 0000 kg
Single ups system100 kVA 1250 kg
 300 kVA 2750 kg
 500 kVA 4250 kg