| Summary of heating and cooling load comparisons at design conditions for 5 m3/s ahu | ||||
| Summer | Winter | |||
| Cooling coil | Heater battery | Cooling coil | Heater battery | |
| Two-wheel ahu | 120 kW | 0 | 0 | 12 kW |
| Conventional ahu | 171 kW | 42 kW | 0 | 102 kW |
| Energy savings at design conditions | 51 kW | 42 kW | 0 | 90 kW |