Table 1: Luminaire control factors | |
Control function | CL |
a) The luminaire is in daylit space (see paragraph 1.45), and its light output is controlled by | 0·80 |
b) The luminaire is in a space that is likely to be unoccupied for a significant proportion ofworking hours and where a sensor switches off the luminaire in the absence of occupants but switching on is done manually | 0·80 |
c) Circumstances a) and b) above combined | 0·75 |
d) None of the above | 1·00 |
Table 2: Maximum area of openings unless compensating measures are taken | ||
Building type | Windows and doors as % of the area of exposed wall | Rooflights as % of area of roof |
Residential buildings (where people temporarily or permanently reside) | 30 | 20 |
Places of assembly, offices and shops | 40 | 20 |
Industrial and storage buildings | 15 | 20 |
Vehicle access doors and display windows and similar glazing | As required |
Table 3: Light sources meeting the criteria for general lighting | |
Light source | Types and ratings |
High pressure sodium | All types and ratings |
Metal halide | All types and ratings |
Induction lighting | All types and ratings |
Tubular fluorescent | 26 mm diameter (T8) lamps, and 16 mm diameter (T5) lamps rated above 11 W, provided with high efficiency control gear. 38 mm diameter (T12) linear fluorescent lamps 2400 mm in length. |
Compact fluorescent | All ratings above 11 W |
Other | Any type and rating with an efficacy greater than 50 lumens per circuit Watt. |
Table 4: Maximum power consumption of high efficiency control gear | |
Nominal lamp rating (W) | Control gear power consumption (W) |
Less than or equal to 15 | 6 |
Greater than 15, not more than 50 | 8 |
Greater than 50, not more than 70 | 9 |
Greater than 70, not more than 100 | 12 |
Greater than 100 | 15 |
Table 5: Light sources meeting the criteria for display lighting | |
Light source | Types and rating |
High pressure sodium | All types and ratings |
Metal halide | All types and ratings |
Tungsten halogen | All types and ratings |
Compact and tubular fluorescent | All types and ratings |
Other | All types and rating with an efficacy greater than 15 lumens per circuit watt. |