Table 1: Luminaire control factors
Control functionCL
a) The luminaire is in daylit space (see paragraph 1.45), and its light output is controlled by
  • A photoelectric switching or dimming control, with or without manual override, or
  • Local manual switching (see paragraph 1.57a)
  • 0·80
    b) The luminaire is in a space that is likely to be unoccupied for a significant proportion ofworking hours and where a sensor switches off the luminaire in the absence of occupants but switching on is done manually0·80
    c) Circumstances a) and b) above combined0·75
    d) None of the above1·00
    Table 2: Maximum area of openings unless compensating measures are taken
    Building typeWindows and doors as % of the area of exposed wallRooflights as % of area of roof
    Residential buildings (where people temporarily or permanently reside)3020
    Places of assembly, offices and shops4020
    Industrial and storage buildings1520
    Vehicle access doors and display windows and similar glazingAs required 
    Table 3: Light sources meeting the criteria for general lighting
    Light sourceTypes and ratings
    High pressure sodiumAll types and ratings
    Metal halideAll types and ratings
    Induction lightingAll types and ratings
    Tubular fluorescent26 mm diameter (T8) lamps, and 16 mm diameter (T5) lamps rated above 11 W, provided with high efficiency control gear. 38 mm diameter (T12) linear fluorescent lamps 2400 mm in length.
    Compact fluorescentAll ratings above 11 W
    OtherAny type and rating with an efficacy greater than 50 lumens per circuit Watt.
    Table 4: Maximum power consumption of high efficiency control gear
    Nominal lamp rating (W)Control gear power consumption (W)
    Less than or equal to 156
    Greater than 15, not more than 508
    Greater than 50, not more than 709
    Greater than 70, not more than 10012
    Greater than 10015
    Table 5: Light sources meeting the criteria for display lighting
    Light sourceTypes and rating
    High pressure sodiumAll types and ratings
    Metal halideAll types and ratings
    Tungsten halogenAll types and ratings
    Compact and tubular fluorescentAll types and ratings
    OtherAll types and rating with an efficacy greater than 15 lumens per circuit watt.