Welcome to building.co.uk. This site uses cookies. Read our policy.

Table 1: Illustrative Cooling Requirements and Running Cost (London Location)
  Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Cooling load (kW) 380 386 398 419 443 470 483 480 462 432 406 388
Running kW fc 37 37 41 86 111 156 163 162 150 99 46 37
Running kW dx 94 94 114 122 139 157 167 160 144 131 116 102
Running cost fc (£) 1465 1465 1614 3388 4387 6180 6465 6423 5935 3936 1809 1465
Running Cost dx (£) 3715 3729 4508 4840 5518 6205 6598 6338 5713 5188 4595 4048
Cooling load 80% (kW) 304 309 319 335 355 376 387 384 369 346 325 311
Running kW fc 80% 37 37 37 81 99 102 134 132 126 82 48 37
Running kW dx 80% 90 87 109 112 125 130 133 130 125 113 108 97
Running cost fc 80% (£) 1465 1465 1465 3208 3901 4039 5306 5227 4990 3274 1891 1465
Running cost dx 80% (£) 3564 3435 4316 4435 4960 5148 5267 5148 4950 4475 4277 3841
Table 2: Average temperatures in London (ºC)
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
4·3 5·1 6·7 9·4 12·5 16·0 17·7 17·3 14·9 11·1 7·7 5·4