Table 1: Maximum design values of Zs at disconnection times of 0·4 and 5 s for Hager BS EN 60 898 devices | ||||||
Type | B curve | C curve | D curve | |||
In | 0·4 s | 5 s | 0·4 s | 5 s | 0·4 s | 5 s |
6 | 8 V | 8·8 V | 4 V | 8·8 V | 2·0 V | 8·8 V |
10 | 4·8 V | 5·33 V | 2·4 V | 5·33 V | 1·2 V | 5·33 V |
16 | 3 V | 3·33 V | 1·5 V | 3·33 V | 0·75 V | 3·33 V |
20 | 2·4 V | 2·66 V | 1·2 V | 2·66 V | 0·6 V | 2·66 V |
25 | 1·92 V | 2·14 V | 0·96 V | 2·14 V | 0·48 V | 2·14 V |
32 | 1·5 V | 1·66 V | 0·75 V | 1·66 V | 0·375 V | 1·66 V |
40 | 1·2 V | 1·33 V | 0·6 V | 1·33 V | 0·3 V | 1·33 V |
50 | 0·96 V | 1·06 V | 0·48 V | 1·06 V | 0·24 V | 1·06 V |
63 | 0·76 V | 0·84 V | 0·38 V | 0·84 V | 0·19 V | 0·84 V |