Table 1: peak winter | |||||||
AHU ref | Volume (m3/s) | Pre-heat required (kW) | Total heating required (kW) | Heat recovered (kW) | (% of total) | ‘Free’ humidification achieved (kg/h) | Approximate humidification power saved (kW) |
AHU 6/1 | 5.15 | 56.75 | 151.35 | 85.76 | 56.7 | 96.21 | 81.78 |
AHU 6/2 | 9.69 | 106.78 | 284.74 | 161.35 | 56.7 | 181.02 | 153.86 |
AHU 6/3 | 10.33 | 113.81 | 303.48 | 171.97 | 56.7 | 192.93 | 163.99 |
AHU 6/4 | 5.31 | 58.49 | 155.99 | 88.39 | 56.7 | 99.16 | 84.29 |
Table 2: PEAK SUMMER | ||||||||||
AHU ref | Volume (m3/s) | ‘Semco’ wheel: anticipated supply air ‘off’ condition | Design: supply air ‘off AHU’ condition | Cooling & dehum recovered (kW) | Cooling & dehum recovered (Kw) | Approximate % peak cooling & dehum saved | ||||
(Db 0C) | (Wb 0C) | Specific enthalpy (kJ/kg) | (Db 0C) | (Wb 0C) | Specific enthalpy (kJ/kg) | |||||
AHU 6/1 | 5.15 | 25.1 | 19.2 | 54 | 18 | 15 | 42 | 125.16 | 31.41 | 25 |
AHU 6/2 | 9.69 | 25.1 | 19.2 | 54 | 18 | 15 | 42 | 235.47 | 59.1 | 25 |
AHU 6/3 | 10.33 | 25.1 | 19.2 | 54 | 18 | 15 | 42 | 250.97 | 62.99 | 25 |
AHU 6/4 | 5.31 | 25.1 | 19.2 | 54 | 18 | 15 | 42 | 128.99 | 32.38 | 25 |