TABLE 1: Maximum instantaneous fan energy and fan energy consumption for 07.00 to 19.00
Test No System
configuration
Maximum Fan
consumption (w)
Fan saving (%) Fan Consumption
07.00 – 19.00 h (kwh)
Fan saving (%)
1 Radial system
sensor in west leg
2160   20.94  
2 Radial system
sensor in east leg
2040 5.50 20.46 2.30
3 Loop system with
sensor in east leg
1800 16.70 19.88 5.10
4 Loop system with
sensor in west leg
1800 16.70 20.00 4.50
5 Loop with sensor
in west end of loop
1800 16.70 19.66 6.10
6 Loop with sensor
in east end of loop
1800 16.70 19.50 6.90