| TABLE 1: Maximum instantaneous fan energy and fan energy consumption for 07.00 to 19.00 | |||||
| Test No | System configuration | Maximum Fan consumption (w) | Fan saving (%) | Fan Consumption 07.00 – 19.00 h (kwh) | Fan saving (%) |
| 1 | Radial system sensor in west leg | 2160 | 20.94 | ||
| 2 | Radial system sensor in east leg | 2040 | 5.50 | 20.46 | 2.30 |
| 3 | Loop system with sensor in east leg | 1800 | 16.70 | 19.88 | 5.10 |
| 4 | Loop system with sensor in west leg | 1800 | 16.70 | 20.00 | 4.50 |
| 5 | Loop with sensor in west end of loop | 1800 | 16.70 | 19.66 | 6.10 |
| 6 | Loop with sensor in east end of loop | 1800 | 16.70 | 19.50 | 6.90 |