| RCD operating time limits | |
| RCD type | Trip time (at 100% of rated operating current) |
| General-purpose rcds to BS 4293 and rcd-protected socket outlets to BS 7288 | Device is required to trip in under 200 ms |
| RCDs to BS 4293 (with time delay) eg 100 ms delay | Device should trip between 200 ms plus 50% of the time delay and 200 ms plus 100% of the time delay eg trip time between 250 ms and 300 ms |
| General-purpose rcds to BS 61 008 and rcbos to BS EN 61 009 | Device should trip in under 300 ms |
| RCDs to BS EN 61 008 and BS EN 61 009 Type ‘S’ | Device should trip between 130 ms and 500 ms |