Keep up to date Table 1: Energy and water quantities at Gelredome Stadium | |
Cooling capacity of heat pump | 332kW |
Heating capacity | 410kW |
Heat production by heat pump | 5400 GJ |
Cold energy by heat pump | 4320GJ |
Summer cold energy demand | 1728 GJ |
Cooling capacity of cold storage | 2800kW |
Groundwater winter flow rate | 1.7 x 10.2m3/s |
Groundwater summer flow rate | 6.9 x 10.2m3/s |
Pumped quantity winter | 175,000 m3 |
Pumped quantity summer | 60,000 m3 |
Injection temperature winter | 7 C |
Injection temperature summer | 15 C |
Water flow temperatures from ground water varies according to season etc. Source: IF Technology | |
Table 2: Energy saving _ comparison with conventional | |
Conventional installation | |
Cooling with chiller | 576GJ |
Heating with gas-fired boiler 80% | 2700 |
Total | 3276GJ |
Ground energy storage with heat pump | |
Cooling with energy storage | 36GJ |
Heating with heat pump and groundwater | 1764GJ |
Total | 1800GJ* |
*A saving of 45%. Source: IF Technology |