- News
All the latest updates on building safety reformRegulations latest
- Focus
- Comment
- Programmes
- CPD
- Building the Future
- Jobs
- Data
- Subscribe
- Events
2024 events calendar
Explore nowBuilding Awards
Keep up to date
- Building Boardroom
All the latest updates on building safety reform
2024 events calendar
Explore nowBuilding Awards
Keep up to dateTABLE 1: ROOF VENT SIZES FOR THE ZERO WIND CASE | ||
Roof vent size (m2) (Door closed on the lowest storey) | Roof vent size (m2) (Door open on the lowest storey) | |
Natural ventilation case | 18·6 | – |
Fire in atrium (50ºC) | 19·4 | 26·3 |
Fire in atrium (60ºC) | 19·7 | 26·7 |
Fire in atrium (70ºC) | 20·0 | 27·1 |
Fire in atrium (80ºC) | 20·3 | 27·5 |
Fire in atrium (90ºC) | 20·6 | 27·9 |
Fire in atrium (100ºC) | 20·9 | 28·3 |