Keep up to dateTable 1: HF lighting load harmonics summary – case study 1 | ||
Voltage (V) | Current (A) | |
RMS | 245·1 | 65·39 |
Peak | 336·5 | 158·08 |
DC offset | -0·4 | -0·35 |
Crest | 1·37 | 2·42 |
THD% rms | 5·98 | 43·54 |
THD% fund | 5·99 | 48·37 |
Hrms | 14·7 | 28·42 |
K factor | 8·77 |
Table 2: Communications room distribution board current and distortion – case study 2 | |||
Red | Yellow | Blue | |
Current (A rms) | 24 | 41 | 53 |
THD (% fundamental) | 50 | 40 | 31 |
Voltage (V rms) | 237 | 238 | 237 |
THD (% fundamental) | 8 | 8 | 8·26 |