| Comparison of CEN and CWCT requirements | ||
| Test | CEN European standard for curtain walling | CWCT UK standard for curtain walling |
| Watertightness | Water flow rate 2 l/min/m2 | Water flow rate 3.4 l/min/m2 |
| Wind resistance serviceability | Limit on deflection of framing members between points of attachment to structure 15 mm | Limit on deflection of framing members between points of attachment to structure 20 mm |
| Residual deflection on unloading less than 5% of maximum | Residual deflection on unloading less than 1 mm | |
| Displacement at fixings to structure not greater than 1 mm | ||
| Load applied once in 25% increments each maintained for 15 seconds | Load applied five times without increments and maintained for three seconds on each application | |
| Repeat airtightness | Air leakage at peak pressure not to exceed result of initial test by more than 0.3 m3/h/m2 | Air leakage to comply with requirements for first test |
| Repeat watertightness | Not required | Required |
| Dynamic watertightness | Optional in all cases | Optional for test pressures less than 600 pa. Required for higher test pressures |
| Roving fan method | Aeroplane engine method | |
| Wind resistance safety | No limit on deflection given | Permanent deformation of framing members shall not exceed 1/500 of the span measured between points of attachment to the building |