| Table 1: HF lighting load harmonics summary – case study 1 | ||
| Voltage (V) | Current (A) | |
| RMS | 245·1 | 65·39 |
| Peak | 336·5 | 158·08 |
| DC offset | -0·4 | -0·35 |
| Crest | 1·37 | 2·42 |
| THD% rms | 5·98 | 43·54 |
| THD% fund | 5·99 | 48·37 |
| Hrms | 14·7 | 28·42 |
| K factor | 8·77 | |
| Table 2: Communications room distribution board current and distortion – case study 2 | |||
| Red | Yellow | Blue | |
| Current (A rms) | 24 | 41 | 53 |
| THD (% fundamental) | 50 | 40 | 31 |
| Voltage (V rms) | 237 | 238 | 237 |
| THD (% fundamental) | 8 | 8 | 8·26 |