| Table 1: Energy and water quantities at Gelredome Stadium | |
| Cooling capacity of heat pump | 332kW |
| Heating capacity | 410kW |
| Heat production by heat pump | 5400 GJ |
| Cold energy by heat pump | 4320GJ |
| Summer cold energy demand | 1728 GJ |
| Cooling capacity of cold storage | 2800kW |
| Groundwater winter flow rate | 1.7 x 10.2m3/s |
| Groundwater summer flow rate | 6.9 x 10.2m3/s |
| Pumped quantity winter | 175,000 m3 |
| Pumped quantity summer | 60,000 m3 |
| Injection temperature winter | 7 C |
| Injection temperature summer | 15 C |
| Water flow temperatures from ground water varies according to season etc. Source: IF Technology | |
| Table 2: Energy saving _ comparison with conventional | |
| Conventional installation | |
| Cooling with chiller | 576GJ |
| Heating with gas-fired boiler 80% | 2700 |
| Total | 3276GJ |
| Ground energy storage with heat pump | |
| Cooling with energy storage | 36GJ |
| Heating with heat pump and groundwater | 1764GJ |
| Total | 1800GJ* |
| *A saving of 45%. Source: IF Technology | |