Table 1: Relative cost and efficiency of recuperator systems (based on 5 m3/s AHU)
Recuperator cost Indicative cost (£) Fan motor power supply/extract (kW) Pump/motor power (kW) Efficiency (%)
Run-around coil 14 000 7·5/6·3 2·1 46
Plate heat exchanger 17 900 7·6/6·0   50 
Thermal wheel 18 000 7·0/8·9 0·15 71
Table 2: Comparative costs of air handling units
Type Duty (m3/s) Unit cost (£) Run-around coil Thermal wheel Plate heat exchanger
Direct gas-fired 2 13 000 14 000 17 000 17 000
5 28 600 31 000 36 000 36 000
10 65 000 69 000 79 000 76 000
15 91 000 98 000 104 000 105 000
lthw coil 2 11 500 13 000 15 000 16 000
(external) 5 25 300 28 000 32 000 32 000
10 57 500 62 000 72 000 68 000
15 80 500 87 000 93 000 94 000
LTHW coil 2 10 000 11 000 14 000 14 000
(internal) 5 22 000 25 000 28 000 28 000
10 50 000 54 000 63 000 61 000
15 70 000 76 000 82 000 93 000
Costs are based upon the fabrication and installation of air handling units for a commercial office building. They are current in December 1999, based on locations in Central London. The costs are based on air handling units containing the following components: supply fan, exhaust fan, heating and cooling coils, bag and panel filters and control panel.