Part L: Fan and system efficiencies for a typical AHU | ||
Unit reference | AHU 1 SUPPLY | AHU 1 EXTRACT |
Design criteria | ||
Design capacity (m3/s) | 22 | 17.1 |
Design static (Pa) | 1089 | 696 |
Quantity of velocity pressures | 1 | 1 |
Max w/l/s | 2.5 | 2.5 |
Max system input power / kw | 55 | 42.75 |
Preselection criteria | ||
Max discharge velocity | 12 | 12 |
Nominal dynamic (based on above discharge velocity) | 86.4 | 86.4 |
Nominal total pressure | 1175.4 | 782.4 |
Nominal required system efficiency to meet pressure | 47.02% | 31.30% |
Selected fan data | ||
Dynamic (Pa) | 112 | 107 |
Shaft power (kW) | 28.4 | 15.84 |
Installed motor power (kW) | 2 x 30 | 2 x 15 |
Fan shaft efficiency | 93.04% | 86.69% |
Based on | 2 x 800 | 2 x 710 |
Motor efficiency (nominal) | 93.40% | 93.40% |
Based on | ||
Belt drive efficiency (nominal) | 94.00% | 94.00% |
Based on | belt drive | belt drive |
Inverter efficiency (nominal) | 96.50% | 96.50% |
Based on Danfoss VLT6000 at 75% load | ||
Total tolerance of fanset components | 0.00% | 0.00% |
Based on | Not considered | Not considered |
Actual system input power (kW) | 33.52 | 18.7 |
Max actual system input power (kW including tolerances) | 33.52 | 18.7 |
System heat loss per volume flow rate (W/ l /s) | 1.52 | 1.09 |
Max (W/ l/s) including tolerances | 1.52 | 1.09 |
Total system efficiency | 78.82% | 73.44% |
Worst case total system efficiency including tolerances | 78.82% | 73.44% |
Reselection criteria | ||
Max static (Pa based on above component efficiencies) | 1858.6 | 1729.1 |
Max total pressure (Pa based on above component efficiencies) | 1970.56 | 1836.11 |
System heat loss per volume flow rate (W / l /s) | 2.3735 | |
(with supply and extract powers/supply air vol) | ||
Heat wheel heat recovery | Winter | 74.30% |
Summer | 76.00% | |
Air Pressure drop on the AHUS | ||
Volume (m3/s) | 22 | 17.1 |
External static pressure (Pa) | 300 | 250 |
Louvre (Pa) | INC | INC |
Damper (Pa) | 40 | 75 |
Electric frost (Pa) | 20 | 0 |
Panel/bag AHU 1 clean (Pa) | 188 | 87 |
Thermal wheel (Pa) | 158 | 117 |
Cooler & eliminator (Pa) | 209 | 0 |
Electric heater (Pa) | 20 | 0 |
Atmospheric attenuation (Pa) | 16 | 14 |
Non-return dampers (Pa) | 70 | 70 |
Diffuser (Pa) | 50 | 45 |
Jobside attenuation (Pa) | 18 | 38 |
Totals | 1089 | 696 |