| Summary of requirements for 30 mA RCD protection | |||
| Regulations | Relating to | Example | Additional protection |
| 411.3.3 | All socket-outlets up to | Downstairs sockets | 30 mA RCD or RCBO |
| 20 A rating for general use | Upstairs sockets | ||
| by ordinary persons | Kitchen sockets | ||
| Cooker outlet with | |||
| integral 13 A socket-outlet. | |||
| Any other socket rated | |||
| up to 20 A including garage. | |||
| 701.411.3.3 | All electrical circuits | Shower circuit | 30 mA RCD or RCBO |
| in a room with a | Lighting circuit | ||
| fixed bath or shower | Heating circuit | ||
| Ventilation circuit | |||
| Shaver socket | |||
| Socket-outlets | |||
| 522.6.6 | All electrical circuits buried | All concealed wiring | 30 mA RCD or RCBO |
| 522.6.7 | in a wall or partition at depth | - Socket-outlets | |
| 522.6.8 | of less than 50 mm and | - Lighting circuits | |
| without earthed | - Smoke alarms | ||
| mechanical protection | - Burglar alarms | ||